For more information email our support team at enquiries@airventtechnology.co.uk or call the Information Hotline on +44 (0)1264 356415

belt driven Plant & Weatherproof

  • "HRP7-HRP8: HRR7-HRR8"

Features - PLANT Models

    • 2 models
    • airflow to 2.0m³/sec
    • wide selection of control panels available
    • EHB or LPHW
    • latent heat exchange with complete separation of supply and exhaust air flows - no cross contamination
    • inlets and outlets fitted with "Mez" type duct connecting flanges
    • rigid casing construction
    • casing can be powder coated to any BS or RAL colour
    • panel filters fit into slide-in channels
    • filter access doors are fitted with quarter turn fasteners - all other removable panels are retained via set screws fitted with weather caps
Heat Recovery belt driven Plant & Weatherproof

Additional Features - WEATHERPROOF Models

    • 2 models
    • air inlets on external units protected by weatherproof cowl and bird guard
    • roof mounted units with plastisol exterior in light grey to BS10A05
    • belt driven Plant & Weatherproof - Additional Features - WEATHERPROOF Models

Specification

    • units are finished in galvanised, double skinned steel with 25mm thick mineral wool slab insulation of 45 kg/m³ density (providing high degree of acoustic insulation) (high density mineral wool and barrier matt or plaster board also available for reduced noise breakout)
    • fans are belt drive double inlet, double width, forward curved centrifugal type, mounted on integral anti-vibration mounts
    • motors - with thermal cut-out protection and a transit bolt fitted to avoid damage in transit
    • cross flow plate heat exchangers are 100% composite construction with efficiencies from 50%. Profiled aerofoil inlets and exits ensure minimum pressure drop and even air distribution. Up to 95% recycled material used in construction - they are 100% recyclable
    • electric heater batteries for 1ph and 3ph operation are manufactured from sheathed rod elements with an integral, manual reset thermal cut-out for wiring into control unit
    • maximum air temperature 50ºC
    • panel filters manufactured from reinforced non-woven media with metal support grid to G4 grade, fitted as standard in easily removable housings. Higher degree of filtration can be provided on request
    • manufactured in UK to ISO 9001

Range

    • PLANT MODELS:

      -  HRP7

      -  HRP8

    • WEATHERPROOF MODELS:

      -  HRR7

      -  HRR8

Heat Recovery Efficiency

      belt driven Plant & Weatherproof - Heat Recovery Efficiency

Performance and Unit Selection

      belt driven Plant & Weatherproof - Performance and Unit Selection

Sound Data - Fan and Filter

      belt driven Plant & Weatherproof - Sound Data - Fan and Filter

Dimensions - Plant Models

      belt driven Plant & Weatherproof - Dimensions - Plant Models

Dimensions - Roof Models

      belt driven Plant & Weatherproof - Dimensions - Roof Models

Electric Heater Battery Data

      belt driven Plant & Weatherproof - Electric Heater Battery Data

Silencers

    • All silencers are sized to match the connection spigot sizes of the main unit. We advise that silencers for use on supply discharge are sized to include a long plenum on the unit side. This 300mm will not increase the attenuation of the silencers.
    • All silencers have:

      -  20mm MEZ flanges

      -  Glass tissue faced pods

      -  Galvanised steel casing

       

    • belt driven Plant & Weatherproof - Silencers belt driven Plant & Weatherproof - Silencers

Control Panel - HRCP (no Heating)

    • Epoxy painted steel enclosure
    • Door interlock isolator
    • Individual switches,and run and trip indicators for fan
    • Panel live indicator
    • Individual fuses for fan
    • Mains input:

      - 400V, 50Hz, 3Ph and N

      - or 230V,50Hz, 1Ph

    • Maximum output:

      -  Fans 3A max FLC supply & extract single phase motors

Control Panel - HRCP-E-Model 1 - Electric Heating

    • Epoxy painted steel enclosure
    • Door interlock isolator
    • Individual switches,and run and trip indicators for fan
    • Panel live indicator
    • Individual fuses for fan and heater elements
    • Mains input:

      - 400V, 50Hz, 3Ph and N

      - or 230V,50Hz, 1Ph

    • Maximum output:

      - Heater 18kW, single phase

      - Fans 3A max FLC supply and extract single phase motors

    • Maximum number of heater steps: 6
    • Fan run-on timer: 2 mins approx
    • belt driven Plant & Weatherproof - Control Panel - HRCP-E-Model 1 - Electric Heating

Control Panel - HRCP-E-Model 2 - Electric Heating

    • Epoxy painted steel enclosure
    • Door interlock isolator
    • Individual switches, and run and trip indicators for fan
    • Panel live indicator
    • Individual fuses for fan and heater element
    • Mains input:

      - 400v, 50Hz, 3ph and N

    • Maximum output:

      - Heater 45kW, three phase

      - Fans 3A max FLC supply and extract single phase motors

    • Maximum number of heater steps: 3
    • Fan run-on timer: 2 mins approx

Control Panel - Hot Water Heating - HPCP-W

    • Epoxy painted steel enclosure
    • Door interlock isolator
    • Individual switches,and run and trip indicators for fan
    • Panel live indicator
    • Individual fuses for fan and heater element
    • Mains input:

      - 400v, 50Hz, 3ph and N

      - or 230V ,50Hz 1ph

    • Maximum output:

      - Fans 3A max FLC supply and extract single phase motors

Control Panel Standard Features and Options

    • Standard Features:

      - 230v face and by-pass damper motor open/close signal

      - Face and by-pass duct stat

      - 7 day time clock

      - BMS enable/volt free contact

      - Frost stat (water heater only)

    • Standard Options:

      - Weatherproofing

      - Frost EHB/LPHW coil

      - Intake and return air shut-off dampers

      - Dirty filter indicators

      - Internally mounted speed controllers

      - Extract run/stand-by auto-changeover for twin fan units

      - 3 phase fan motors

Leaflet

Manuals